Low Frequency Online UPS Of Cybercon

   Technical Specification of 1 Phase Online UPS
Input Voltage Range 170V-280V(Other Ranges on Request)
Battery Voltage 48 V -180 V
Output Voltage 230V± 1%V Ac
Output Waveform Pure Sine Wave
Protections DC High & Low Voltage Output under Voltage, Over Voltage, Overload & Short Circuit
Hormonic Distortion Less than 3%
Efficiency (max.)

>90% for 180V DC 
>85% for 48V DC/72V/120V DC 

Power Factor 0.8 Lagging to Unity
Overload 100% for 10 min.
200% for 5 Cycles or
as per requirement
Overload

110% for 10 min.
200% for 5 Cycles 
400% for 1/2 Cycles or 
as per requirement

Crest Factor >4:1
Transient Recovery Within 3 Cycles
Audible Noise Less than 50db at 1 Metre Upto 10Kva
   Technical Specification of 3 Phase Online UPS
   INPUT CONDITIONS & SPECIFICATIONS
Voltage

Three phase, 415V(-20% to + 10%)
330V to 470V AC

Frequency 50Hz±10% (45-55Hz)
Rectifier/ Charger 12 Pulse Full Control Rectifier along with input isolation transformer.
Current Distortion Less than <10% THD in normal condition  & rated full load.
Power Factor

Better than 0.8 LAG at normal & rated load

Input Cut-off Automatic cut off for input under /over voltage, single phase, Phase reversal condition
Surge Protection Sustain Input surges without damage as per standards
Battery Charging

Automatic Float cum Boost charger
Constant voltage constant current type

Normal DC Voltage 380/384V
Battery Type Suitable for all type of Batteries
Battery Charging Selectable 2/4/8A
Current Normally 4.0A (in Battery charging) Mode.
Transient Voltage ± 5% under 80% step load change
Transient Recovery Upto 80% within 10 msec.
Crest Factor Better Than 3.0
Overload

120% for 10 min                                          
150% for 10 Cycles 
200% for Instantaneous trip

Circuit Method On-Line PWM UPS, Zero Transfer Time
Control Method Sinusoidal PWM control switching
Frequency 12 KHz Modulated over 50.00Hz
Temprature 0-50 Degree centigrade at ambient
Humidity 95% RH Max ( Non Condensing)
Acoustic Noise Less than 65 dBA at a distance at 1 Metre.
Cooling Natural/Forced air type  for inverter
Output Station Output Isolation Transformer between inverter & Load
   LED INDICATIONS ON FRONT PANEL
   RECTIFIER INPUT STATUS
LI Mains On L2 D.C ON
L3 Battery on Charge L4 Battery Charged
L5 Rectifier Trip L6 Input OV
L7 Input UV L8 DC OV
L9 Alarm On L10 Inv On
L11 Mains Fail L12 Auto off
L13 Alarm ON L14 System Trip
L15 Battery Low L16 Output OV
L17 Output OV L18 Output OC
   INVERTER TECHNOLOGY INVOLVED
Output/ Inverter I.G.B.T High Frequency double edge PWM Converter
Technology VLSI/FPGA based total software Control
Phase Balancing Capable for 100% unbalance load conditions at output with power factor 0.65 to unity
By Pass Inverter is Continuously tracking bypass input frequency within specified limits         
By pass input may be stabilized with servo stabilizer & Isolation transformer another UPS
System.
Isolation Double Wound Isolation Transformer between Inverter & output with Galvanic isolation.
   STATIC SWITCH CHANGE OVER (OPTIONAL)
Change over switch Thyristorised Static Switch
Rating Capable of 300% Overload Load Capacity
Transfer / Retransfer Automatic Bi-directional
Change Over Period Sync. Mode—Within 2mSec
   DISPLAY ON LCD METER
Display 16 x 2 Alphanumeric
Display on LCD Input Voltage RY, YB, BR, RN, YN, BN Bypass Input Voltage Ry, YB, BR, RN, YN< BN, Input Frequency / Output Frequency Battery Charge in Percentage & V/Cell Output Voltage RY, YB, BR, RN, YN, BN, Load on System in Percentage RYB Phase.
  PROTECTIONS PROVIDED TO RECTIFIER SECTION
INPUT, RECTIFIER & DC LINK NATURE OF PROTECTION
Input Under Volt Electronic

Input Over Volt

Electronic

Input Over Current

Circuit Breaker (Fuse less)

Input Phase Fail

Electronic

Input Phase Reverse

Electronic

DC over Volt

Electronic

Battery Over Current

Fuse

  SMART MONITORING SOFTWARE (OPTIONAL)

UPS

COMPUTER

Input Voltage

Analog/Digital Display

Bypass Input Voltage

Analog/Digital Display

Input Frequency

Analog/Digital Display

Battery Charge

Bar Graph/ Percentage

Output Voltage

Analog/ Digital Display

Event log Book

Log Book of All Events Right from all Voltages Frequencies, Load & Battery Status on Every Event

  PROTECTION PROVIDED TO INVERTER

INVERTER/ OUTPUT

NATURE OF PROTECTION METHOD

Inverter Input Fuse

Semiconductor Fuse( Fast Blow)

Output Under Volt

Electronic( Inverter Shut Down)*

Output Over Volt

Electronic( Inverter Shut Down)*

Output Over Current

Electronic(Inverter Shut Down)*

Output Short Circuit

Electronic (Fuse Less)

Battery Over Discharge

Electronic (Inverter Shut Down)*

*Incase of Inverter Shut Down load is transfer to bypass input through static switch

  INDICATIONS STATIC SWITCH SECTION (OPTIONAL)

BYPASS STATIC SWITCH BYPASS STATIC SWITCH
L 19   Load On- UPS L 21 Bypass – Over Volt (Fault)
L 20   Load On -Bypass L 22 Bypass    Under volt (Fault)

   SWITCH GEAR & DISTRIBUTION UNIT

INPUT, RECTIFIER & DC LINK

INVERTER / STATIC SWITCH

Input MCCB/ MCB

Output MCCB

Fuses to Each Semiconductor

Fuses to all Inverter IGBT

Battery MCCB / MCB

Bypass Input MCCB / MCB

Fuse to Battery Input

Fuses to all Static Switch Thyristors

AC DB Unit at output (Optional)

Custom Built

Output Conditions & Specifications

Load Rating

100% Continuous

Output Voltage

230Volts±1%Neutral-line

Regulation

400Volts±1% Line-Line for 100% unbalanced load.

Frequency

50Hz±1Hz to 3 Hz in synchronous condition.                
50Hz±0.1Hz in Asynchronous condition

Power Factor

0.8 Lag of Unity

Phase displacement & imbalance

Less than 19 on 100% balance & rated load.                       
Less than 20 on 100% Unbalance & rated load.

Wave form distortion

Pure sine wave <3% at full load (Non Linear) Load) 2% Linear Load

 Automatic Line Drop Compensation

0 to ± 0.5% of Nominal Voltage on Output Voltage

Inverter Efficiency

More Than 90%